Castle Series C6KVA-C10KVA

Power Range:4200W-7000W

Type:Online

Description:The Castle series On-line UPS is an advanced true double conversion On-line Topology,the Castle Isolated gate Bipolar Transistors (IGBT) for true isolation from AC input.Ideal for Data Centers in network and Industrial applications.Features scalable battery packs for those critical business systems that require long run times.

contact now





    • Features
    • Specifications
    Servers, Data centers, Critical network devices, Sensitive electronic equipment, Telecom.
    • Online Double conversion
    • Non transfer time of output
    • PFC technology
    • Full digital control (DSP)
    • Output power factor: 0.8
    • Input current harmonic: 5%
    • Charging /Rectifier/Inverter fully digital control technology
    • Economic Operation Mode (ECO)
    • Optimization battery group: 16/18/20 pieces (optional)
    • Wide voltage range: 120VAC-276VAC
    • Wide input frequency range: 40Hz-70Hz
    • Self-testing when UPS startup
    • Input over/under-voltage protection
    • Automatic Bypass
    • Cold start (DC)
    • Fault isolation
    • Comunication port: RS232 port, dry contact, RS485*2
    • Optional: SNMP card/Centralized monitoring card/ Parallel port module
    High Frequency Online UPS Castle Series UPS C6KVA/C6KS  C10KVA/C10KS
    Output
    Output  C6KVA/C6KS C10KVA/C10KS
    Rated Power 6000VA/4200W 10000VA/7000W
    Output Voltage  208VAC/220VAC/230VAC/240VAC
    Voltage Waveform Pure Sine wave
    Crest Factor 3:01
    Output Frequency
    (Synchronized- Mains) 
    46~54Hz or 56Hz - 64Hz (Line mode)
    50/60HZ/ ±0.05Hz( Battery mode) 
    Regulation(Nominal) ±1%
    Regulation(Battery mode)  ±1%
    Transfer time  AC to DC :Zero           Inverter to Bypass: Zero
    Over current protection Line Mode:10min@100%~130%;Battery Mode:30s@100%~130%
    Outlet  Hard Wiring with Terminal Block 
    Harmonic Distortion  ≤2%THD(Linear Load);≤5%THD(Non-Linear Load)
    Input 
    Nominal Voltage 160~300VAC@full load (110~300VAC@half load)
    Input Frequency  46~54Hz / 56~60Hz
    Efficiency  90% (AC mode)   90%(Battery Type)
    Noise Filtering  Full time EMI/RFI filtering
    Over current protection  by AC fuse    or by re-settable over current   protector 
    AVR Range
    (2 Bucks,2 Boosts) 
    Enhanced Buck: +15% of selected nominal voltage
    Buck mode: +5% of selected nominal voltage
    Boost mode: -5% of selected nominal voltage
    Enhanced Boost: -12.5% of selected nominal voltage
    Phase Single phase with ground
    Battery 
    Battery type  Sealed Lead Acid Battery
    Rated Charging Voltage  220.8Vdc
    Typical backup time  >5min
    Charging method  Smart pulse charging with two charging modes.
    Quick charging when battery is not fully charged,
    trickle charging when battery is 90% fully charged.
    Charging current(MAX) 1.0A(6KS,10KS:4.0/8.0A)
    Protection  Over current protection &
    Over charging voltage protection (SCR control)
    Thermal protection (CPU control)
    When temperature inside UPS is over 45℃,charger will stop 
    charging for 2.5 minutes followed by an 1.5 minutes charging.
    The cycle will be repeated until the temperature is lower than 44℃.
    Temperature
    Compension 
    Yes
    Numbers of
    Battery
    20
    Optional Features 
    ECO Mode Support
    CVCF Support
    PDU Support
    Remote Panel  Wired Type,Up to 100M Length
    Parallel Redundancy  Up to 4 Units maxium(Option)
    Up to 4 Units maxium(Option)
    Environmental and Safety 
    Operating Temperature   0℃ to 40℃ (32℉ to 104℉)
    Transit/storage
    Temperature 
    -15℃ to 55℃(5℉ to 131℉)
    Relative Humidity  20-90%(NON-CONDENSING)
    Operating Altitude  0 ~ 3000 meters
    Audible noise ≦50 dBA
    Safety Markings  BSMI CE
    EMC Class B, EN50091-2, FCC part15, IEC1000-2-2
    Quality control system ISO 9001:2000
    Noise Level  <60dB@1 Meter
    Indicator
    LED Version  Load Level/Battery Level/Battery;Mode/AC Mode/Bypass Mode/Fault
    Battery Mode  Sounding every 4 seconds
    Low Battery  Sounding every second
    Overload   Sounding twice every  second
    Fault  Continously Sounding 
    Interface 
    Smart RS-232  Software supports Windows Family.Sun Solaris,
    IBM Aix,Compaq True64,SGIIRIX ,FreeBSD.HP-UX,and MAC
    USB (Option)  Windows Family& MAC
    Internal Slot (Option)  SNMP/AS400 Relay Card/Rs485
    EPO(Option)  Support Emergency Shutdown
    Physical 
    Dimensions:
    (D×H×W)
    570*260*717mm
    N.W/G.W(kg)  6KVA:90  6KS:35 10KVA:93  10KS:38
    Packing  standard Packing,Export carton for each unit

    ------Separator----------------------------