MD–A series 1-20k VA Sine phase ups

Power Range:1-20KVA

Type:Online

Description:MD series 1/1 UPS ensure maximum protection and power quality for any type of load, especially for mission critical applications, security systems and electro-medical equipment, industrial processes and telecommunications.

contact now





    • Features
    • Specifications
    • IT device;
    • Date center;
    • Precision instrument;
    • Bank computer;
    • Electric factory;
    • Industry and so on.
    • Input voltages : 1 phase 220V/230v/240v or 1 phase 110v/120v
    • Built-in output isolation transformer
    • True double-conversion on line UPS
    • Distributed or centralised parallel up to 6 units per redundant (N+1) or powerparallel.
    • Perfect medium power protection with redundancy for mission critical load, server room, data center, and telecom applications
    • Temperature compensation and deep discharge protection to reduce overall battery ageing 7.Advanced RS232 communication, multiplatform, for all operating systems and network environments
    • Both Remote led mimic panel & graphic display
    • Can be set to ECO
    • Sixth generation IGBT, much higher efficiency, lowe temperaturer, more reliable
    • Cold start
    • Generator compatible
    • Option SNMP and dry contact connection
    Model MD-A1KL MD-A2KL MD-A3KL MD-A5KL MD-A6KL MD-A8KL MD-A10KL MD-A15KL MD-A20KL
    VA rating 1KVA 2KVA 3KVA 5KVA 6KVA 8KVA 10KVA 15KVA 20KVA
    Working mode and principle
    True on–line
    AC input
    Phase L + N + G
    Voltage 110/120V or 220/230/240VAC ± 25%
    Frequency 50/60Hz ± 5%
    Power factor 0.92 (with input filter)
    Soft start 0 – 100%  5 s (non-shock current)
    Bypass input
    Phase Single phase
    Voltage 110/120V or 220/230/240VAC ± 20%
    Frequency 50/60Hz ± 5%
    Transfer time 0 UPS, Inverter / bypass (overload)
    DC system
    DC voltage 48V 192V (rated voltage)
    42V 168V (end voltage)
    AC output
    Phase Single phase
    Voltage 110/120V or 220/230/240VAC ± 1%(stable load); 110/120V or 220/230/240VAC ± 5%(load fluctuation)
    Frequency 50/60Hz ± 0.05% (battery mode)
    Power factor 0.8
    Wave form Pure sine wave
    Harmonic distortion <3%(linear load); <5%(non-linear load)
    Dynamic Dynamic load voltage instaneous change(0-100%)   ± 5%
    Time Instaneous recover time  <10 mS
    Overload 125% for 10 min; 150% for 1min,200% for 1min
    Cooling Force ventilation
    System
    Efficiency 85% 86% 90% 92% 93% 93% 93% 95%
    Communication RS232、RS485、SNMP (options)
    Temperature 0-40℃ (working)
    Humidity 30-90%
    Working height < 1000m (1% power reduce per 100 m height rising, Max. 4000m)
    Noise(db) 40-55 45-60 50-65
    Dimension(mm) 210×500×530 220×560×610 305×585×740 380×680×950
    Weight(KG) 51 58 65 70 73 85 108 265 300
     
    ------Separator----------------------------