This Online Series is an uninterruptible power supply incorporating double-conversion technology. It provides perfect protection specifically for computer equipment, Communication Systems to computerized instruments.The double-conversion principle eliminates all mains power disturbances. A rectifier converts the alternating current from the utility power to direct current . This direct current charges the batteries and powers the inverter. On the basis of this DC voltage. the inverter generates a sinusoidal AC voltage which is constantly powering the loads.Computers and Peripherals are thus powered entirely by the UPS. In the event of power failure, the maintenance-free batteries power the inverter.
MODEL | 6KRS 0.8 | 6KRS 0.9 | 6KRS 1.0 | 10KRS 0.8 | 10KRS 0.9 | 10KRS 1.0 |
---|---|---|---|---|---|---|
Input | ||||||
Power rating | 6KVA/4.8KW | 6KVA/5.4KW | 6KVA/6KW | 10KVA/8KW | 10KVA/9KW | 10KVA/10KW |
Nominal Voltag | 208/220/230/240VAC | |||||
Input Voltage Range | 110~300VAC (176~288vac) | |||||
Current (176Vac) | 29.0A max | 32.5A max | 36.0A max | 48.0A max | 54.0A max | 60.0A max |
Frequency Range | 50Hz: 44~56Hz/60Hz: 54~66Hz | |||||
Power Factor | ≧ 0.985 | |||||
Harmonic Distortion | ≤5% (Linear Load) ≤8% (Non-linear Load PF=0.7) | |||||
Output | ||||||
Voltage | 208/220/230/240VAC | |||||
Current (220Vac) | 21.81A max | 24.54A max | 27.27A max | 36.36A max | 40.9A max | 45.45A max |
Voltage Regulation | ±1% | |||||
Frequency Range | Line Mode: Synchronized range, Battery Mode: 50/60Hz±0.1% | |||||
THD | ≤2% (Linear Load) ≤5% (Non-linearLoad) | |||||
Battery Input | ||||||
Battery | 192VDC(Default); 216VDC; 240VDC | |||||
Battery Current | 26.6A | 30A | 33A | 44.3A | 50A | 55.5A |
AC Charger | ||||||
Charging Current | 1~12A (Saettable) | |||||
Physica | ||||||
Overlord Capacity | Line Mode: 30min@102%~110% Load / 10min@110%~130% Load / 30s@130%~150% Load / 500ms@>150% Load Battery Mode: 10min@102%~110% Load / 1min@110%~130% Load / 10s@130%~150% Load / 500ms@>150% Load | |||||
Transfer Time | 0ms | |||||
Efficiency | AC Mode: Peak efficiency 95.5%. Full load efficiency 95%. | |||||
Operating environment | ||||||
Temperature | 0℃ ~40℃ | |||||
Humi dity | 20%~95% | |||||
Altitude | <1000m | |||||
Storage temperature | -15~40℃ | |||||
Dimension(D*W*H), mm | 482*400*86 | |||||
N.W(kg) | 12kg | |||||
Battery Pack | ||||||
Type | External Battery Pack | |||||
Nominal DC Voltage | 192VDC | |||||
Backup Time (Full load) | 7 min (with 1BP) | |||||
Net Weight (kg) | 51.36 | |||||
Dimension W*H*D(mm) | 483*130*600(3U) |