EH9500 3/3 External Battery Series (20-60/100/200KVA)

Modular UPS

The EH9500 modular series uses advanced "N+X" wireless parallel Redundancy technology to support 4 parallel connections. The system is easy to upgrade,expand and maintain, has excellent electrical performance, high system availability,and complete software and hardware protection.Power modules, monitoring modules,power distribution modules,maintenance bypass switches, and output switches provide safe and reliable ower protection for various loads.


  • DSP full digital control technology
  • Input power factor up to 0.99
  • Parallel modules share the same battery pack
  • “N+X” wireless parallel redundancy technology
  • Advanced battery intelligent management technology

Live Chat Contact Us

-->

Standard Product Details


Features

  • DSP full digital control technology, pure online double conversion architecture, with strong carrying capacity;
  • Adopt standard cabinet,and the power distribution system is integrated inside the cabinet, which is convenient to install and saves user’s investment;
  • Input power factor up to 0.99, low harmonic current, environmental protection, high efficiency and energy saving;
  • Wide input voltage range, 50Hz/60Hz grid system adaptive, suitable for various environmental grids;
  • “N+X” wireless parallel redundancy technology, it is easy to set the number of redundant parallel units through the LCD screen; all modules support hot swap operation for easy maintenance;
  • Advanced battery intelligent management technology (automatic floating charge switching, battery pack temperature compensation, etc.) to effectively extend battery life;
  • With distributed bypass power supply, each module has built- in automatic bypass switch and corresponding bypass current sharing inductor, which provides good current sharing of system bypass power supply;
  • Parallel modules share the same battery pack, saving user battery investment;
  • With emergency shutdown (EPO) switch and remote emergency shutdown (REPO) function;
  • Perfect software and hardware protection functions (C-level lightning protection, air-opening, Fuse, hardware protection, software protection), super self-diagnosis function, rich history query;
  • Large LCD touch widescreen display for a friendly human- machine interface;
  • Rich communication interface, including RS232, RS485, USB, dry contact, and SNMP (optional) card;
  • Different external batteries can be selected according to user needs (32/34/36/38/40 pcs);
  • Support battery cold start and city power self-start function to meet user needs With maintenance bypass, when there is an emergency, you can switch to the maintenance bypass power supply, and the maintenance personnel can safely perform online maintenance;
  • Each module adopts an independent control system. The UPS module is independently controlled according to the shared information. After the faulty module fails, it can be disconnected from the parallel system immediately, which does not cause harm to the parallel system.

Applications

Data center integrated computer room, large central network computer room, government department, ISP service provider, telecommunications, finance,securities, transportation,taxation, medical system,etc.

ModelEH9500-60KVA/20EH9500-100KVA/20EH9500-200KVA/20
Capacity
Module No.RU-20 (18KW)
Maximum Number of Modules3510
Input
Input3Ph+N+PE
Rated Voltage380/400V/415Vac
Voltage Range208~478Vac
Frequency Range40~70Hz
Power Factor≥0.99
Bypass Range80 upper limit:25%( +10% ; +15% ; +20% optional)
400 upper limit(20% ; +10% ; +15% optional)
415 upper limit(15% ; +10% optional) lower limit : -45%
(-20%;-30% optional) Bypass frequency protection range: ±10%
Harmonic distortion(THDi)≤ 3% (100% non-linear load)
Generator accessSupport
Output
Output3Ph+N+PE
Rated Voltage380/400V/415Vac
Voltage Regulation±1%
Output FrequencyAC ModeSynchronous with input;
when the mains frequency exceeds the maximum ±10% (±1%, ±2%, ±4%, ±5% can be set),
the output frequency is 50×(±0.2%)Hz
Battery Mode(50/60±0.2%)Hz
Crest Factor3:1
Transfer TimeAC mode to bypass mode: 0ms (tracking); AC mode to battery mode: 0ms
Overload CapabilityLoad≤ 110% for 10min, ≤ 125% for 1min, ≥ 150% turn to bypass mode immediately
Harmonic distortion(THDi)≤ 2%(100% Linear load)
Others
EfficiencyNormal Mode 95%
CommunicationInterfaceRS232 RS485 2 Intelligent Slot (Smart card slot) dry connect
Executive StandardCE,EN/IEC 62040-2, EN/IEC 62040-1-1, YD/T1095-2008
Battery
Battery Voltage±192V±204V±216V±228V±240V DC;
(32 pcs;34 pcs;36 pcs;38 pcs;40 pcs optional)
Charging CurrentUPS Cabine30A Max.50A Max.100A Max.
Power Module10A Max.
Working Environment
Operating Temperature0℃ ~ 40℃
Relative Humidity0 ~ 95% non condensing
Stored Temperature-25℃ ~ 55℃
Altitude< 1500m
Physical Characteristics
Physical Dimension (D×W×H)mmCabinet600 x 840 x 1400600 x 1100 x 2000
Module580 x 443 x131(3U)
Net Weight (kg)Cabinet157169306
Module33

    Name*